GETTINGSTARTED(continued) StepFour
FILLusedtocontrolapumpthatfillsatank.
Typically,RelayONistheLOWsetpointandRelayOFFtheHIGHsetpoint.Relaywill
energizeatthelowsetpoint(ON)andremainonuntilthelevelreachesthehighset
point(OFF)andwillremainoffuntilthelevelreturnstothelowsetpoint(ON).
DELAY usedas a start pump delay when the ON setting isreached.The delay pump(in
seconds)willdelaythestartofthevalueforthisperiod.
o VALVEValveoperationallowsfortwoseparatelevelsetpoints(RelayONandRelayOFF).Choose
betweentheEMPTYorFILLoperation.BothoperationsrequiresettingalevelforONandanother
levelforOFF
EMPTYusedtocontrolavalvethatemptiesatank.
Typically,RelayONistheHIGHsetpointandRelayOFFtheLOWsetpoint.Relaywill
energizeatthehighsetpoint(ON)andremainonuntilthelevelreaches thelowset
point(OFF)andwillremainoffuntilthelevelreturnstothehighsetpoint(ON).
FILLusedtocontrolavalvethatfillsatank.
Typically,RelayONistheLOWsetpointandRelayOFFtheHIGHsetpoint.Relaywill
energizeatthelowsetpoint(ON)andremainonuntilthelevelreachesthehighset
point(OFF)andwillremainoffuntilthelevelreturnstothelowsetpoint(ON).
DELAY used as a start valve delay when the ON setting is reached.The delay value (in
seconds)willdelaythestartofthevalueforthisperiod.
