RevA MN300282 15of34
CONFIGURATION(cont.) StepFive
HowtosetaPUMPtoEMPTY
Beforestarting,taketwo measurements.1)Measurethe distance
fromthebottomofthetanktothePumpONposition.2)Measure
thedistancefromthebottomofthetanktothePumpOFFposition.
PumpONwillbephysicallyhigherthanthePumpOFFposition.
1. InTOP‐LEVELMENUmode,selectRELAY1,RELAY2orRELAY3.
2. SelectPUMP.
3. SelectEMPTY.
4. SelectON.
5. UsingtheUPandDOWNbuttons,settheONsetpointfortherelay.
6. To enter the value, press and hold SELECT for 2 seconds and
release.SAVEDwilldisplay.
7. SelectOFF.
8. UsingtheUPandDOWNbutto ns,settheOFFsetpointforth erelay.
9. To enter the value, press and hold SELECT for 2 seconds and
release.SAVEDwilldisplay.
Note:If you want toaddadelay when the PUMP starts,continue
ontostep10.Ifnodelayisrequired,jumptostep13.
10. SelectDELAY.
11. UsingtheUPandDOWNbuttons,settheDELAYtimeinseconds.
a. Pumpdelaycanbesetfrom0to600seconds.
12. Toenterthevalue,pressandholdSELECTfor2secondsandrelease.SAVEDwilldisplay.
13. SelectEXITtoreturntoTOP‐LEVELMENU.
Note:Tospeedupthescrollingofthevaluesonthedisplay,holddowntheSELECTbuttonwhileholdingdown
theUPorDOWNbuttons.