Flowline LU78 EchoSwitch Manual do Utilizador Página 11

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 34
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 10
RevA MN300282 11of34
CONFIGURATION(cont.) StepFive
HowtoconfiguretheOperationalrangeofEchoSwitch®
Before starting, take two measurements.1) Measure the
distancefromthebottomofthesensor (transducerface)tothe
bottomofthetank.ThiswillbetheHEIGHTsetting.2)Measure
thedistancefromthebottomofthetanktotheMaximumLevel
ofLiquid(Full).ThiswillbetheFILLHsetting.
1. InTOPLEVELMENUmode,selectTANK.
2. SelectHEIGHT.
3. Using the UP and DOWN buttons, set the HEIGHT of the
tank(transducerfacetothebottomofthetank).
4. To enter the value, press and hold SELECT for 2 seconds
andrelease.SAVEDwilldisplay.
5. WhenFILLHappears,pressSELECT.
6. UsingtheUPandDOWNbuttons,setthe FillHeight(FILL
H) of the tank (max. level of liquid to the bottom of the
tank).
7. To enter the value, press and hold SELECT for 2 seconds
andrelease.SAVEDwilldisplay.
8. SelectEXITtoreturntoTOPLEVELMENU.
Note:The Height and FillHeight (FillH) settings also determine the 4 to 20 mA current span.The Height
settingdeterminesthe4mApositionandtheFillHsettingdeterminesthe20mAposition.
Note:Tospeedupthescrollingofthevaluesonthedisplay,holddowntheSELECTbuttonwhileholdingdown
theUPorDOWNbuttons.

Vista de página 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 33 34

Comentários a estes Manuais

Sem comentários